Outside of working and dedicated space needs there are many special considerations for electrical rooms that depend on building programs as well as exterior.
Electrical room door fire rating requirements.
You are correct that electrical vaults containing equipment with 600 amps or greaters must have at least 3 hour rated walls and 3 hour rated floors if there are any floors underneath the vault.
Please note that electrical room may require fire rated walls see nfpa 110 5 2 1 5 2 2.
1 1 1 with the exception of fabric fire safety curtain assemblies this standard addresses assemblies that have.
Where equipment rated 1200 a or more that contains overcurrent devices switching devices or control devices is installed and there is a personnel door s intended for entrance to and egress from the working space less than 7 6 m 25 ft from the nearest edge of the working space the door s shall open in the direction of egress and be.
Nfpa 75 appendix c fig b 1.
This standard regulates the installation and maintenance of assemblies and devices used to protect openings in walls floors and ceilings against the spread of fire and smoke within into or out of buildings.
Locating electrical rooms next to these especially if placed between should be carefully evaluated to ensure there is enough space and flexibility for conduits.
A 1 1 see annex k for general information about fire doors.
These electrical rooms are small 2 hour fire rated enclosures entered by a 90 minute fire rated door from each floor and the floor slab penetration of the vertical cables or busbars rising along the building through the corners of these rooms are horizontally sealed by 2 hour fire rated mortar.